Fire-Resistant Doors: Are Belgian Rf Ratings Obsolete?

Since 1 July 2022, doors carrying the Belgian classes Rf 1⁄2h or Rf 1 h can no longer be installed in the new buildings. They must now conform to the European classification. However, we must remain vigilant, because not all European classes are accepted in our country. Thus, only doors bearing the European classes EI₁ 30, EI₁ 60 or EI₁ 120 can be installed in new buildings!

Y. Martin, Ir., Strategy and Innovation Coordinator and Technical Committee Coordinator, Buildwise
D. De Bock, ing., and G. De Raed, ing., Senior Advisers, Technical Advice and Consultation Division, Buildwise
S. Eeckhout, ing., Senior Project Manager, Acoustics, façades and carpentry division, Buildwise

Can Rf ½ h doors still be installed in new Belgian buildings?

No, this is no longer permitted in buildings whose licence application date was submitted after June 30, 2022.

The European fire resistance classification of construction products now replaces the national classes. This amendment, valid for all construction products, has been incorporated into the Belgian fire regulations. So far, however, fire resistant doors were an exception to the rule. Indeed, in view of the confusion found in the CE marking of fire-resistant interior doors, the sector had obtained an extension of the transition period of several years. As a result, the Rf 1⁄2h or Rf 1 hour interior doors could still be marketed and placed on site. For new buildings falling within the scope of Belgian legislation, it is now over.

What criteria do European ratings use?

For elements having a separation function between two fire-resistant spaces or compartments, the European standard distinguishes among others the following criteria:

  • Fireproofness or to flames (E)
  • thermal insulation (1)
  • on thermal radiation (W)
  • smoke-tightness (S).

A ‘subtility’ was introduced with regard to the criterion of thermal insulation (1) of fire-resistant doors. There are two options: I₁ or I₂, the former being more severe than the latter (see NIT 234, § 4.3.2.2).

Which ratings does Belgian law require?

The requirements for the new buildings are reflected in the Royal Decree ‘Basic Standards’, which requires the Class El,. If Belgium has opted for the most severe class, it is necessary, however, to qualify. Indeed, the duration of fire resistance required for the door is often half that required for the wall in which it is placed (e.g. an El door, 30 in an EI₁ 60 wall). This flexibility is not usually found in our neighbours, who have adopted the other, less severe classes (e.g. EI₂ or EW). It should be noted that all doors to stairwells in high buildings must also be smokeproof and therefore require the El class, 30 S200. Class S200 limits the smoke leakage rate to a temperature of 200 °C. The aim is to provide even better protection for stairwells in high buildings, places to be preserved by all means for the evacuation of occupants and the intervention of fire services.

Why do we still find BEN0R-ATG approvals valid after 2022 for Rf 1⁄2h doors?

These doors can still be installed in Belgium in one of the following three situations:

  • in buildings not required to comply with the order
  • Royal ‘Basic Standards’ (e.g. single-family homes)
  • in buildings to be built whose licence application was submitted before 1 July 2022
  • replacement of Rf doors placed in a building built before 1 July 2022.

Can I install EW or EI₂ doors from overseas suppliers in Belgium?

No! Belgian regulations have never allowed the placement of these types of fire resistant doors.

EI₁ doors are the most efficient in the market. They can therefore be used in all cases, even if less severe classes are prescribed (e.g. EI₂ or EW). But the opposite is not allowed! It is not permitted, for example, to place an EW 30 door if the requirement is EI₁ 30.

Moreover, the levels of performance – and therefore of protection – are very different. Thus, through an EW 30 door (mainly marketed in the Netherlands), the radiation of up to 15 kW/m2 is limited to 1 m for 30 minutes. However, this radiation value is sufficient to initiate the combustion of a wooden element less than one metre from the door! There is no need to make it clear that it does not provide sufficient protection for those who are in the vicinity of the emergency or intervention services …

Is a 30-minute claim on a data sheet sufficient?

No, because the information provided is insufficient. It should be verified that it is class EI₁ 30 and not class EW 30 or EI₂ 30.

Is CE marking mandatory for fire-rated doorsets?

As stipulated in Buildwise 2019/02.04, when fire resistant, outdoor pedestrian doorsets and industrial, commercial and garage doorsets must be CE marked since November 1, 2019 (see diagram below).

The situation for doorsets and interior door vants resistant to pedestrian fire has not changed since the publication of the above article: their CE marking is not currently possible.

However, contrary to what was announced in the article, the transition period between the Rf classes and the El classes, is now over. The Rf classes are permanently obsolete for door vants and fire resistant doorsets placed in new buildings, regardless of the possibility and requirement of CE marking.